Document verified compressor thresholds and readable alarm badges

This commit is contained in:
2026-10-25 02:05:38 +00:00
parent 5b801b939c
commit 0171afcf57
3 changed files with 36 additions and 0 deletions
+4
View File
@@ -1,5 +1,9 @@
# Current handoff
## Mandel tuning and badge improvements — October 24, 2026
See MANDEL-TUNING.md. Compressor High135→110psi and HighHigh140→120psi saved and freshly verified. User said ignore unavailable 100psi operating target. Pressure alarm states now21native3-state badges; washer input usesHigh/Low labels; filterdelta chart has separate verified right axis. Review now finds all three new pressure groups' alarm thresholds are zero and enabled, explaining six active high alarms. Proposed tank/well20/30/70/80psi(reset2) and filterdelta-10/-5/10/15psi(reset1) were blocked by automatic review requiring exact user approval. Asked user to approve exact values; pending, none applied. Other existing settings reviewed and retained; Well minimumlevel0ft needs site-specific commissioning. No mode/enable/run/calibration/reset/acknowledge changes.
## Live review follow-up — October 24, 2026
User reported variables working and requested assessment. Read-only review confirmed Well pressure readouts and three-series history now populate. Observed snapshots: tank 49.4–50.1 psi, well about 50.6 psi, differential 0.6–1.2 psi; consistent with well minus tank within display rounding/asynchronous updates. Pump Off, flow 0.0 gpm, water level 54.6 ft. This idle snapshot does not establish filter restriction under flow or physical sensor calibration.