docs: record verified KAV East Water Well 30 trend-label fix

This commit is contained in:
2026-10-21 18:53:37 +00:00
parent e3f3f84e59
commit 0a86c43046
4 changed files with 15 additions and 10 deletions
+9 -6
View File
@@ -2,7 +2,11 @@
Last updated: 2026-10-21 (America/Edmonton)
## Latest completed change — Well 10 chlorine binding
## Latest completed change — East Water Well 30 trend label
On October 21, 2026, corrected production https://www.atomhmi.com/site_kav_east_water/page_wells, Trend element 95ec8b60-2fe9-462d-8222-f2c069e41560. Renamed only the series bound to water:g_well30_flow_out_eu from Well 29 to Well 30. Saved the element/page, freshly reloaded/reopened configuration, and verified only the series name differs among 11 captured form controls (10 series retained). The live chart legend separately shows Well 29 and Well 30. Register, scale gpm, color #b8c564, axes, range buttons and navigator preserved; no register/operational writes. Updated KAV-GUIDE.md, SITE-STUDY.md, PROJECT.md and the relevant cloud guides. Local screenshot: /tmp/kav-east-water-well30-trend-fixed.jpg (not committed).
## Previous completed change — Well 10 chlorine binding
On October 21, 2026, the user authorized correcting production https://www.atomhmi.com/site_kav_water/ Well 10 New (well_10_new). Element Chlorine Current PPM / visible Target ppm, ID 4f503dce-01d9-4339-9d14-8668186b2cea, now has updateRegister water:g_well10ChemPPM instead of water:g_well1ChemPPM. Its display already referenced Well 10. Saved the element and page, observed Successfully Saved Page, then freshly reloaded/reopened and compared all 37 configuration controls: only updateRegister changed. No chlorine value, live register write or operational dosing test was submitted. KAV-GUIDE.md, SITE-STUDY.md, PROJECT.md and their relevant cloud notes updated. Evidence screenshot retained locally at /tmp/kav-well10-chlorine-fixed.jpg (not committed).
@@ -21,13 +25,12 @@ Atom GIT connection recovered. Read repository AGENTS.md, PROJECT.md, HANDOFF.md
Verified page Title/URL and visible element structure; native Copy root identity checked before interpreting JSON. Findings distinguish this session's inspections from October 20 register/alarm observations. No production page saves/pastes, register/setpoint writes, operational buttons, device actions, alarm modifications or live control tests. No raw JSON/credentials/camera/map endpoints uploaded. Browser timeouts were recovered with clean Configure Pages reloads.
## Remaining findings — unchanged by the chlorine correction
## Remaining findings — unchanged by the KAV corrections
1. Lazy B Well 3: Time Since Start and editable Hours use water:wellNW1_tssTmr / wellNW1_totalTmr, unlike other Well 3 bindings.
2. KAV East Water Wells: final Well 29-labeled trend series targets water:g_well30_flow_out_eu.
3. Lazy B: duplicate main/Main navigation targets; M03 PID Tn suffix KP; Loadout internal 100% Button name on an 80-value command. Internal names are not behavioral proof.
4. Lone Pine dryer uses legacy (Dont Use) components. Inspect supported semantics before reusing/migrating.
5. Alarm latching, notification policies, PLC interlocks and operational write behavior were not audited here.
2. Lazy B: duplicate main/Main navigation targets; M03 PID Tn suffix KP; Loadout internal 100% Button name on an 80-value command. Internal names are not behavioral proof.
3. Lone Pine dryer uses legacy (Dont Use) components. Inspect supported semantics before reusing/migrating.
4. Alarm latching, notification policies, PLC interlocks and operational write behavior were not audited here.
## Next task