docs: record Lazy B Well 3 timer register audit and missing mapping

This commit is contained in:
2026-10-21 18:58:02 +00:00
parent 0a86c43046
commit 140c7e93c0
4 changed files with 11 additions and 5 deletions
+2 -2
View File
@@ -57,7 +57,7 @@ Copied operating row contains 55 elements:
Current flow/level chart navigator is water:aiWell3Flow_eu. Historical level navigator is water:aiWell3LvlAgg_Past24Avg, default button index 1. The information/map/report root is separate; preserve it during control-page replacement and do not publish its location details unnecessarily.
**Unresolved timer reference:** Well 3's Time Since Start reads `water:wellNW1_tssTmr * 1000`; editable Hours reads `water:wellNW1_totalTmr * 1000` and writes `value / 1000` to `water:wellNW1_totalTmr`. These names differ from the Well 3 family. Verified in copied JSON; intended PLC mapping remains unknown. No reset/write was made.
**Timer repair pending verified PLC tags — October 21, 2026:** rechecked production Well 3 (`well_3`). Time Since Start, element `6e6f612c-c2e5-4ee9-a468-849e6191b523`, still reads `|{register:water:wellNW1_tssTmr}| * 1000`, non-editable, HH:mm:ss, blank updateRegister. Hours, element `4e613f5b-e0e3-4526-88dd-b9a81695d75e`, still reads `|{register:water:wellNW1_totalTmr}| * 1000`, editable, writes `value / 1000` to `water:wellNW1_totalTmr`, format d [days] HH:mm. Captured both original configurations and left them unchanged. The Water System (water) register table contained 1,660 entries; searches for tss, totalTmr, runtime and wellNW1 returned no matches. The Well 3 family has no verified replacement for either timer. Existing enabled `iWell3Vol_rtDaily[0]` / `[1]` are daily counters, not established equivalents of time-since-start or lifetime Hours; units were not independently verified. `well3Power_total_onTime` exists disabled and is likewise not a verified replacement. Disabled `well3_i_UTS` has blank description, slave Well Shack 2080-LC20-20QBB, address well3.i.UTS; its role/units do not establish a timer binding. Do not invent well3_tssTmr/well3_totalTmr mappings or enable an unrelated counter. Requested the correct PLC tags, units and lifetime-counter write semantics from the user. No page/register saves, counter resets, polling changes or operational tests were performed.
## Valve, compressor and boiler
@@ -104,4 +104,4 @@ Loadout controls M41:
## Future use
Use Main/Settings for navigation context, the specific well for water, Receiving/Reclaim for sequence controls, and Grain Motors for individual equipment. Diagnostics contains consequential maintenance actions; inspect its element configuration without clicking the operational buttons. Treat alarms pages as UI content, not an audit of Manage Alarms definitions. Test-named pages are existing content, not authorized disposable pages.
Use Main/Settings for navigation context, the specific well for water, Receiving/Reclaim for sequence controls, and Grain Motors for individual equipment. Diagnostics contains consequential maintenance actions; inspect its element configuration without clicking the operational buttons. Treat alarms pages as UI content, not an audit of Manage Alarms definitions. Test-named pages are existing content, not authorized disposable pages.