docs: record Lazy B Well 3 timer register audit and missing mapping
This commit is contained in:
+1
-1
@@ -10,7 +10,7 @@ Catalogs now cover 202 pages: KAV Main Mill 43, East Mill 4, Main Water 29, East
|
||||
|
||||
Scope was production Configure Pages and native Copy inspection only. No pastes, site saves, register writes, device actions or operational tests. Development equivalence was not checked. User's two work environments are dev.atomhmi.com and atomhmi.com (observed production host www.atomhmi.com).
|
||||
|
||||
Follow-up correction, October 21, 2026: the user authorized fixing production KAV Main Water Well 10 New. Its chlorine field's updateRegister changed from water:g_well1ChemPPM to water:g_well10ChemPPM, matching its display expression. The page saved successfully; a fresh reload/reopen confirmed persistence and only this field changed among 37 captured form controls. No chlorine setpoint value was submitted or dosing behavior tested. See KAV-GUIDE.md. The preceding read-only scope describes the baseline survey, before this separately authorized configuration edit. Remaining unchanged finding: Lazy B Well 3 timers reference wellNW1. The East Water Well 30 trend label was subsequently corrected in a separately authorized edit; see the dated Trends and history note below.
|
||||
Follow-up correction, October 21, 2026: the user authorized fixing production KAV Main Water Well 10 New. Its chlorine field's updateRegister changed from water:g_well1ChemPPM to water:g_well10ChemPPM, matching its display expression. The page saved successfully; a fresh reload/reopen confirmed persistence and only this field changed among 37 captured form controls. No chlorine setpoint value was submitted or dosing behavior tested. See KAV-GUIDE.md. The preceding read-only scope describes the baseline survey, before this separately authorized configuration edit. Lazy B Well 3 timer repair remains pending: the October 21 register audit found no configured tss/totalTmr/wellNW1 registers and no verified equivalent. The page was left unchanged; correct PLC tags, units and write semantics were requested. See LAZY-B-GUIDE.md. The East Water Well 30 trend label was subsequently corrected in a separately authorized edit; see the dated Trends and history note below.
|
||||
|
||||
## Original October 20 coverage
|
||||
|
||||
|
||||
Reference in New Issue
Block a user