# Shop PLC dashboards
|
||||
|
||||
Built October 21, 2026 for https://dev.atomhmi.com/site_atom/. Device ID `shop`, display name Shop.
|
||||
|
||||
## Scope and inventory
|
||||
|
||||
The register table contains 2,472 entries. The equipment/system inventory saved in `artifacts/shop/register-inventory.json` contains 264 non-alarm-manager entries, including 233 `g_` entries. Alarm-manager internals were excluded from selection, pages, settings, trends, and alarms. No `atGVL_alarmManager` register or its configuration was modified.
|
||||
|
||||
All equipment registers used were already enabled. No enable or recording configuration changes were necessary. Existing operating setpoints, alarm thresholds, alarm-source enables, calibration, and output states were preserved. Runtime entry dialogs were opened and cancelled; no PLC setpoint or output commands were submitted during this build.
|
||||
|
||||
## Published pages
|
||||
|
||||
| Page | Route | Content |
|
||||
| --- | --- | --- |
|
||||
| Overview | page_overview | Default page; office/shop temperatures, heat targets, heat-pump/window output statuses, equipment links and combined temperature history |
|
||||
| Office Heating | page_office_heating | Office temperature; editable heating setpoint/deadband; demand/output/fault; temperature and target trend; four temperature limits and individual hysteresis; four controller alarm-reporting enables |
|
||||
| Floor Heating | page_floor_heating | Shop temperature; editable floor heat target/deadband; demand/output/fault; trend; four limits/hysteresis and alarm-reporting enables |
|
||||
| Window Actuator | page_window_actuator | Office temperature; editable automatic window setpoint/deadband; open/close solenoid status and faults; temperature/target trend |
|
||||
| Temperature Trends | page_temperatures | Office vs shop temperature, office heating/window targets, and floor-heating target history; 1H/1D/7D selectors |
|
||||
| Diagnostics | page_diagnostics | Two temperature sensor/channel/overrange/underrange fault groups, raw inputs, electrical signals/supplies, and two I/O card faults |
|
||||
|
||||
Native Copy/Paste component trees are saved as `artifacts/shop/*-template.json`. New navigation entries were added with Overview as default. The Atom HMI brand link opens the default page.
|
||||
|
||||
## Register map
|
||||
|
||||
All references below use `shop:`.
|
||||
|
||||
- Office temperature: `g_teOffice_out_eu`; shop temperature: `g_teShop_out_eu`.
|
||||
- Office heating: `g_officeHeatCtrl_sp`, `g_officeHeatCtrl_db`, demand `g_officeHeatCtrl_Q`; actual output `g_officeHeat_out_val`, fault `g_officeHeat_fault_out`.
|
||||
- Floor heating: `g_shopFloorCtrl_sp`, `g_shopFloorCtrl_db`, demand `g_shopFloorCtrl_Q`; output `g_shopFloor_out_val`, fault `g_shopFloor_fault_out`.
|
||||
- Window control: `g_windowSP`, `g_windowDB`; solenoid outputs `g_officeWndOpen_out_val`, `g_officeWndClose_out_val`; corresponding `_fault_out` registers.
|
||||
- For each temperature prefix `g_teOffice` / `g_teShop`, limits use `_limits_{lo,lolo,hi,hihi}_in_sp`, individual hysteresis `_in_hyst`, controller reporting enables `_alm_in_en`, and HMI alarm sources `_alm_out`.
|
||||
- Temperature diagnostics use `_sensorFault_out`, `_faults_chan_out`, `_faults_over_out`, `_faults_under_out`; raw/signal/supply use `_in_raw`, `_in_signal`, `_in_supVlt`.
|
||||
- Hardware faults: `g_base1_card01_fault_out`, `g_base1_card02_fault_out`.
|
||||
|
||||
Numeric settings read the register and write `value` back to the same register. Deadband/hysteresis entry limits are 0–100 °C; operating setpoints and thresholds retain signed numeric entry. Two-position alarm switches use 1 enabled / 0 disabled. They change PLC alarm reporting enable inputs, distinct from the HMI alarm definition's enabled setting.
|
||||
|
||||
## Alarms
|
||||
|
||||
Created 22 HMI alarms from existing PLC fault and limit alarm outputs: 8 temperature-limit alarms, 8 temperature-input/sensor faults, 2 heating-output faults, 2 window-solenoid faults and 2 I/O card faults. All 22 were reopened and verified enabled/non-latching. Update interval 1 second, HMI delays 0; PLC source logic retains its existing delays. High/Low temperature alarms are Warning; High-High/Low-Low and faults are Critical. Alarm and return-to-normal messages identify equipment in plain language. No notification group was selected, and no external notification recipients were configured.
|
||||
|
||||
The full alarm manifest and verification is `artifacts/shop/alarms-created.json`. No alarms were generated from alarm-manager internals or reset/acknowledgement globals.
|
||||
|
||||
## Commissioning notes
|
||||
|
||||
- Existing temperature limits are 0 °C. These were exposed rather than replaced with invented thresholds. Set coherent operating limits before relying on temperature alarming. HMI alarms follow existing `_alm_out` signals; HMI non-latching does not change PLC latching/source logic.
|
||||
- `g_teShop` descriptions incorrectly repeat Office temperature. Page/alarm names follow the distinct Shop register prefix and control-loop mapping.
|
||||
- No separate boiler-water temperature or boiler operating target was found. Floor Heating shows the floor loop's room-temperature demand and pump output; it does not claim to provide direct boiler control.
|
||||
- Window open/close signals are solenoid output commands. No position-feedback register was found. Do not label these as confirmed fully open/closed or offer direct output writes without establishing control logic.
|
||||
- Heating demand and pump output are deliberately separate. At inspection the floor demand was 1 with pump output 0; this build does not establish the interlock or pump-feedback behavior.
|
||||
- Runtime counters `_out_rt` exist but their time units are not documented, so no guessed hours conversion was added.
|
||||
- Historical chart loading takes longer than live numeric polling. Wait for plotted traces, not only axis labels, before recording QA screenshots.
|
||||
|
||||
## Verification and artifacts
|
||||
|
||||
- Saved and opened all six pages; overview showed live office ~23.7–23.8 °C, shop ~18.5 °C and both heating targets 20 °C.
|
||||
- Confirmed plotted sensor/target history on the Temperature Trends page.
|
||||
- Opened Heating Setpoint at 20 °C and Window Setpoint at 22.5 °C; cancelled both.
|
||||
- Reopened every new alarm and checked its ID, enabled=true and latching=false.
|
||||
- Screenshots include overview.jpg, office-heating.jpg, floor_heating.jpg, window_actuator.jpg, temperatures.jpg, diagnostics.jpg and alarms.jpg. Early runtime-audit snapshots can contain temporary polling placeholders; final trend screenshot shows loaded traces.
|
||||
|
||||
Use ATOMHMI-PLAYBOOK.md for the general Copy/Paste, modal, and navigation editing workflow.
|
||||