docs: document 30 verified Highway 21 well card fault alarms
This commit is contained in:
+15
-1
@@ -1,5 +1,19 @@
|
||||
# Current handoff
|
||||
|
||||
## Card fault alarms completed — October 26, 2026
|
||||
|
||||
After the user imported the updated PLC XML, Water had 2,798 register definitions. The imported names use the correctly spelled suffix unlatched: GVL_Well[n]_out_flow_flt_card_unlatched and GVL_Well[n]_out_lvl_flt_card_unlatched, for n=0–14. Their OPC UA addresses follow Application.GVL.Well[n].out.{flow,lvl}.flt.card.unlatched on Water PLC.
|
||||
|
||||
Enabled polling for all 30 well card-fault sources, preserving On Change and one-second intervals. Fresh table readback verified all 30 Enabled Yes; the settled snapshot showed 0 for 29 sources, with the most recently enabled level source still blank at capture. No PLC values were written. The separate cistern card-fault definition was outside this well-specific request and remained disabled.
|
||||
|
||||
Created 30 enabled HMI alarms, bringing Water from 26 to 56 definitions. IDs CARD-00-FLOW/CARD-00-LEVEL through CARD-14-FLOW/CARD-14-LEVEL use the user's mapping above. Program10 is Well18 and program11 Well19. Programs12–14 are explicitly named Spare Program12–14. Descriptions follow “Well 5 Flow Input Card Fault” / “Well 5 Level Input Card Fault”. Messages are quoted expression strings, for example "Well 5: flow input card fault detected. Check the input module and its connection." Return text: "Well 5: flow input card fault has cleared."
|
||||
|
||||
Each calculation directly references |{register:water:GVL_Well[n]_out_flow_flt_card_unlatched}| or the corresponding lvl source. Settings: Warning, Enabled true, HMI Latching false, one-second update interval, Delay On0, Delay Off0; notification groups Default and Atom Notifications, matching the existing sampled well alarm.
|
||||
|
||||
Validation: reloaded the alarm page and reopened all 30 saved forms. Verified every ID, description, calculation, fault message, return message, enabled/latching state, interval, delays and notification groups. Filter CARD- returned exactly30 rows; total56. Existing26 descriptions/messages were retained, including the previously recorded Well18/19 discrepancy. No alarm conditions forced, reset/acknowledgement or notification-delivery test performed. Polling configuration and persisted alarm definitions are verified; physical card failure behavior is not tested.
|
||||
|
||||
Local deliverables: highway-21-card-alarms.png and highway-21-card-alarm-audit.json in this chat's outputs directory.
|
||||
|
||||
## Highway 21 card fault source audit — October 26, 2026
|
||||
|
||||
Read shared instructions and cloud index; no existing Highway 21 guide. Created HIGHWAY-21-GUIDE.md and cloud guide https://chatgpt.com/space/page_068c2a277110819180a2c5853c714e99, indexed both. User mapping recorded, including index10 Well18 and index11 Well19. Water catalog2,766 registers; card search zero; unlatched170; fault60 VFD entries. Exact inspected flow fault source Application.GVL.Well[0].out.flow.flt.chan.unlatched is disabled, On Change1s. Water has26 alarms. Existing index10/11 low-flow/low-level descriptions swap Well19/18 relative to user mapping; retained. User confirmed new PLC tags require importing. Native Water PLC import requires OPC UA XML; no tag browser. Awaiting export XML or full exact paths and equipment/card assignments. Delete Unused defaults ON; turn OFF for additive work. No tags or alarms added. No site configuration or PLC values saved. Next: resolve exact sources, add/verify alarms, update guides and commit completion.
|
||||
@@ -172,4 +186,4 @@ Use Atom GIT to open Auto/atom-hmi-ui-chatgpt on master. Read AGENTS.md, PROJECT
|
||||
|
||||
### Alarm history lookup — October 21, 2026
|
||||
|
||||
User requested checking whether any Bin G alarm previously occurred. Opened the alarm icon → Alarm History at https://www.atomhmi.com/site_sweetgrass/alarm_history. Requested Last 30 Days (September 22–October 21, 2026), then freshly reloaded and requested October 21, and finally Yesterday (October 20). Every attempt remained on Loading... without a history table, records, or an explicit empty-result message. No browser warning/error logs were captured. Occurrence, timestamps and retention therefore remain unverified; this is not evidence of no prior Bin G alarms. No acknowledgement, reset, alarm edits, register writes or page saves performed. User-confirmed update on October 21, 2026: Atom HMI was just updated and alarm logs moved to a new database; previous history is no longer available. This supersedes the earlier plan to retry for pre-migration records. Historical Bin G occurrences cannot be determined from the current database. The migration explains unavailable prior history, but the cause of the observed Loading... UI was not independently established. The intended Bin G enable/disable alarm path remains unresolved; determine it from current configuration or user/PLC confirmation.
|
||||
User requested checking whether any Bin G alarm previously occurred. Opened the alarm icon → Alarm History at https://www.atomhmi.com/site_sweetgrass/alarm_history. Requested Last 30 Days (September 22–October 21, 2026), then freshly reloaded and requested October 21, and finally Yesterday (October 20). Every attempt remained on Loading... without a history table, records, or an explicit empty-result message. No browser warning/error logs were captured. Occurrence, timestamps and retention therefore remain unverified; this is not evidence of no prior Bin G alarms. No acknowledgement, reset, alarm edits, register writes or page saves performed. User-confirmed update on October 21, 2026: Atom HMI was just updated and alarm logs moved to a new database; previous history is no longer available. This supersedes the earlier plan to retry for pre-migration records. Historical Bin G occurrences cannot be determined from the current database. The migration explains unavailable prior history, but the cause of the observed Loading... UI was not independently established. The intended Bin G enable/disable alarm path remains unresolved; determine it from current configuration or user/PLC confirmation.
|
||||
+16
-2
@@ -1,6 +1,6 @@
|
||||
# Highway 21 site guide
|
||||
|
||||
Verified October 26, 2026 (America/Edmonton). Production target: https://www.atomhmi.com/site_highway_21/page_well_14. Site ID highway_21; device selector Water. This session inspected configuration only; no alarms, registers, polling, PLC values or pages were saved.
|
||||
Verified October 26, 2026 (America/Edmonton). Production target: https://www.atomhmi.com/site_highway_21/page_well_14. Site ID highway_21; device selector Water. Updated after user import: all 30 well card-fault alarms created and verified; polling enabled for their 30 sources. Earlier discovery notes below describe the pre-import state.
|
||||
|
||||
## Program mapping confirmed by user
|
||||
|
||||
@@ -30,10 +30,24 @@ Opened GVL_Well[0]_out_flow_flt_chan_unlatched: slave Water PLC; address {"tag":
|
||||
|
||||
Water has 26 HMI alarm definitions: 12 well low-flow, 12 well low-level, and cistern high/low-level. Existing well entries for index 10 say Well 19 and index 11 say Well 18, opposite the user's mapping. This discrepancy was observed and left unchanged pending scope resolution.
|
||||
|
||||
## Requested card fault alarms pending source clarification
|
||||
## Historical card fault import preparation
|
||||
|
||||
User confirmed these are new PLC tags requiring import. Native Manage Registers → Import → Water → Water PLC → Normal accepts an OPC UA XML file; no live tag browser is exposed. Import defaults observed: Delete Unused ON, Enabled OFF, On Change one second. Turn Delete Unused OFF for additive imports and inspect the validation preview before submission. Awaiting PLC export XML or exact full fault.card.unlatched paths and equipment/card assignments. No tags or alarms added. After receiving the source data, import only missing definitions, add equipment-specific alarm descriptions and quoted Message/Return to Normal expressions, verify persistence, and update this guide.
|
||||
|
||||
## Target page observations
|
||||
|
||||
Well 14 has flow in gpm, water level in ft, totals in gal, time displays, level/flow trends, and low-flow/low-level enable, threshold and delay controls. Read-only snapshot: 0.0 gpm, water level 8.7 ft. No runtime controls operated. Existing alarm create form supports calculation, importance, latching, on/off delays, notification groups and enabled state; opening a draft was inspection only.
|
||||
|
||||
## Card fault alarms completed — October 26, 2026
|
||||
|
||||
After the user imported the updated PLC XML, Water had 2,798 register definitions. The imported names use the correctly spelled suffix unlatched: GVL_Well[n]_out_flow_flt_card_unlatched and GVL_Well[n]_out_lvl_flt_card_unlatched, for n=0–14. Their OPC UA addresses follow Application.GVL.Well[n].out.{flow,lvl}.flt.card.unlatched on Water PLC.
|
||||
|
||||
Enabled polling for all 30 well card-fault sources, preserving On Change and one-second intervals. Fresh table readback verified all 30 Enabled Yes; the settled snapshot showed 0 for 29 sources, with the most recently enabled level source still blank at capture. No PLC values were written. The separate cistern card-fault definition was outside this well-specific request and remained disabled.
|
||||
|
||||
Created 30 enabled HMI alarms, bringing Water from 26 to 56 definitions. IDs CARD-00-FLOW/CARD-00-LEVEL through CARD-14-FLOW/CARD-14-LEVEL use the user's mapping above. Program10 is Well18 and program11 Well19. Programs12–14 are explicitly named Spare Program12–14. Descriptions follow “Well 5 Flow Input Card Fault” / “Well 5 Level Input Card Fault”. Messages are quoted expression strings, for example "Well 5: flow input card fault detected. Check the input module and its connection." Return text: "Well 5: flow input card fault has cleared."
|
||||
|
||||
Each calculation directly references |{register:water:GVL_Well[n]_out_flow_flt_card_unlatched}| or the corresponding lvl source. Settings: Warning, Enabled true, HMI Latching false, one-second update interval, Delay On0, Delay Off0; notification groups Default and Atom Notifications, matching the existing sampled well alarm.
|
||||
|
||||
Validation: reloaded the alarm page and reopened all 30 saved forms. Verified every ID, description, calculation, fault message, return message, enabled/latching state, interval, delays and notification groups. Filter CARD- returned exactly30 rows; total56. Existing26 descriptions/messages were retained, including the previously recorded Well18/19 discrepancy. No alarm conditions forced, reset/acknowledgement or notification-delivery test performed. Polling configuration and persisted alarm definitions are verified; physical card failure behavior is not tested.
|
||||
|
||||
Local deliverables: highway-21-card-alarms.png and highway-21-card-alarm-audit.json in this chat's outputs directory.
|
||||
|
||||
+1
-1
@@ -87,4 +87,4 @@ ARCO-POULTRY-GUIDE.md documents production site_arco_poultry/page_barn_4. All 22
|
||||
|
||||
## Highway 21 — October 26, 2026
|
||||
|
||||
Production site_highway_21 has a new HIGHWAY-21-GUIDE.md and cloud guide https://chatgpt.com/space/page_068c2a277110819180a2c5853c714e99. User program-to-well mapping recorded. Requested card-fault alarm additions await exact-source clarification; current register catalog has no card-named entries. See guide for verified counts and existing Well18/19 description discrepancy.
|
||||
Production site_highway_21 has a new HIGHWAY-21-GUIDE.md and cloud guide https://chatgpt.com/space/page_068c2a277110819180a2c5853c714e99. User program-to-well mapping recorded. After the user imported the updated tags, created and reopened all30 well level/flow card-fault alarms (56Water total) and enabled their30 polling sources. Programs12–14 are labelled spares; program10 Well18 and program11 Well19. See guide for verified counts and existing Well18/19 description discrepancy.
|
||||