docs: record Arco Poultry Barn 4 register enable audit
This commit is contained in:
@@ -0,0 +1,39 @@
|
||||
# Arco Poultry guide
|
||||
|
||||
Verified October 22, 2026 (America/Edmonton).
|
||||
|
||||
## Target and scope
|
||||
|
||||
Production: https://www.atomhmi.com/site_arco_poultry/page_barn_4.
|
||||
Device: barn_controller (Barn Controller). All 22 distinct registers used by Barn 4's supported data components belong to slave barn_3_4, whose current UI label is Barn 3. This label alone does not establish physical equipment ownership.
|
||||
|
||||
Inspected all 25 Numerical Data, Indicator and Trend forms (17 numeric displays, five indicators, three trends), including chart series and navigator references and the pressure setting write target. Configure Pages title Barn 4 / URL barn_4 verified. Its root dd6ff64a-49d8-4ae8-9052-7944ccb1f4d3 retains the internal name Barn 3; an undefined [object Object] child 9cb6da86-c4c2-4065-984a-72ed256a1b47 is present with no established supported data behavior. No page edits or saves were made.
|
||||
|
||||
## Register enable changes
|
||||
|
||||
Eight used definitions changed from enabled=false to true through Manage Registers. Fresh page reload and individual form readback verified all eight; comparison of captured input/select controls showed only Enabled changed. All retain ON_CHANGE at one second, Modbus unit 1, bit number 0 and swapped=true.
|
||||
|
||||
| Register | Display | Modbus type / address / format |
|
||||
| --- | --- | --- |
|
||||
| PLC1Inlet1PosPerc | Ceiling inlet position (%) | holding / 10512 / float |
|
||||
| PLC1Inlet2PosPerc | Wall inlet position (%) | holding / 10526 / float |
|
||||
| qcBn4Heat1 | Heat Stage 1 status | coil / 207 / bit |
|
||||
| qcBn4Heat2 | Heat Stage 2 status | coil / 108 / bit |
|
||||
| qcBn4CircFan | Circulation fans status | coil / 206 / bit |
|
||||
| FeedBn4Total | Total feed (Kg) | holding / 11812 / float |
|
||||
| FeedBn4TotalTdy | Total feed today (Kg) | holding / 11814 / float |
|
||||
| PLC1BirdAge | Bird age (Days) | holding / 10600 / int |
|
||||
|
||||
The other 14 used definitions were already enabled and left unchanged: PLC1aicPress, PLC1PressSP, aqcBn4Var1, aqcBn4Var2, aqcBn4Var3, qcBn4SSfan1, qcBn4SSfan2, aicBn4Te1, aicBn4Te2, aicBn4Te3, TeBn4Avg, mbmNetStat1, mbmNetStat2, mbmNetStat4. Fresh individual form inspection confirmed all 22 used definitions enabled with ON_CHANGE polling at one second.
|
||||
|
||||
## Bindings and verification
|
||||
|
||||
All references use device prefix barn_controller. Inlet trend uses PLC1aicPress plus both inlet positions; navigator PLC1aicPress. Fan trend and numeric displays use aqcBn4Var1–3; navigator aqcBn4Var1. Temperature trend uses aicBn4Te1–3 and TeBn4Avg; navigator TeBn4Avg. Pressure SP displays and writes PLC1PressSP. Other numeric fields are read-only. Indicators use qcBn4SSfan1–2, qcBn4Heat1–2 and qcBn4CircFan. Communications use mbmNetStat1/2/4.
|
||||
|
||||
Fresh runtime navigation populated the previously blank inlet/feed/age displays: ceiling inlet 41.7%, wall inlet 0.0%, total feed 62411.8 Kg, feed today 848.9 Kg and bird age 184 Days in the observed snapshot. Newly enabled status registers read 0 (Off). Values naturally change.
|
||||
|
||||
Temp 1 remains -999.0 °C despite its register already being enabled; this task did not diagnose its sensor/controller cause. The static-pressure chart series is labelled psi while its axis and numeric field indicate inH₂O; preserved and not independently resolved. Physical mappings, units and controller logic were not commissioned. Trend history retention was not changed or independently verified.
|
||||
|
||||
Only register Enabled flags changed. No setpoint values, PLC commands, resets, alarm definitions, connections, addresses or polling intervals were changed. Unused definitions, including similarly named PLC1TeBn4Avg and sex-specific feed totals, were left unchanged. Scope is the supplied Barn 4 page, not a site-wide audit.
|
||||
|
||||
Local evidence: /tmp/arco-barn4-register-audit.json and /tmp/arco-barn4-enabled.png. These artifacts are not committed and may not persist across hosts.
|
||||
+9
-1
@@ -1,6 +1,14 @@
|
||||
# Current handoff
|
||||
|
||||
Last updated: 2026-10-21 (America/Edmonton)
|
||||
Last updated: 2026-10-22 (America/Edmonton)
|
||||
|
||||
## Arco Poultry Barn 4 registers — October 22, 2026
|
||||
|
||||
Completed production https://www.atomhmi.com/site_arco_poultry/page_barn_4. Inspected all 25 supported data-component forms and identified 22 distinct barn_controller registers. Enabled eight previously disabled definitions: PLC1Inlet1PosPerc, PLC1Inlet2PosPerc, qcBn4Heat1, qcBn4Heat2, qcBn4CircFan, FeedBn4Total, FeedBn4TotalTdy, PLC1BirdAge. Other 14 were already enabled. Fresh reload plus individual form readback confirmed all 22 enabled, ON_CHANGE at one second. Captured input/select comparison for the eight edits showed only Enabled changed. No operational writes or page saves.
|
||||
|
||||
Fresh runtime shows inlet positions, feed totals and age populated (41.7%, 0.0%, 62411.8 Kg, 848.9 Kg, 184 Days in the observed snapshot); status registers read 0. Temp 1 remains -999 °C despite already enabled polling. Sensor cause, pressure chart psi/inH₂O label discrepancy, physical mappings and trend retention remain unresolved/unverified and were not modified. Scope is Barn 4, not all site pages. No follow-up needed for the requested enable audit.
|
||||
|
||||
Created ARCO-POULTRY-GUIDE.md with full used-register map, exact changed addresses and verification limits. Cloud guide https://chatgpt.com/space/page_3952221801fc8191a490c36a1be0c0c5 created and indexed. Local evidence /tmp/arco-barn4-register-audit.json and /tmp/arco-barn4-enabled.png is not committed. Browser is on Barn 4.
|
||||
|
||||
## Motor RPM trends added — October 21, 2026
|
||||
|
||||
|
||||
@@ -80,3 +80,7 @@ Current status — October 21, 2026: the user deleted and retired Demo (site_dem
|
||||
October 21 Gladacres check: all 30 diagnostic/maintenance entries are enabled and Terminal is configured as {}. The native Device Status page and Atom dashboard both populated readings without any saved configuration change (CPU 63.7 °C, HMI 1012 observed). Most diagnostics poll every 600 seconds; uptime is configured for 10 seconds but was about 2–5 minutes old during checks. Initial blank register-table values were not proof of a complete outage. Delayed uptime reporting remains unexplained; no agent/connection cause or repair was established. No commands, resets, updates, reboots, service restarts or log uploads. See GLADACRES-GUIDE.md.
|
||||
|
||||
Cloud guide: https://chatgpt.com/space/page_31b800d9541c8191b7eddf6ee2fac319
|
||||
|
||||
## Arco Poultry — October 22, 2026
|
||||
|
||||
ARCO-POULTRY-GUIDE.md documents production site_arco_poultry/page_barn_4. All 22 used registers on barn_controller / slave barn_3_4 (UI label Barn 3) are enabled with one-second ON_CHANGE polling after enabling eight disabled entries. Fresh readback and runtime verification completed; inlet/feed/age readings populated. Temp 1 remains -999 °C and pressure chart label units differ from its axis/numeric display; causes unresolved. Scope is Barn 4 only. Cloud guide: https://chatgpt.com/space/page_3952221801fc8191a490c36a1be0c0c5.
|
||||
|
||||
@@ -9,6 +9,7 @@
|
||||
"LAZY-B-GUIDE.md": "page_de033ca7a7b881918b94f89dddea9820",
|
||||
"LONE-PINE-GUIDE.md": "page_814209734aa88191bede6b68a663098e",
|
||||
"SWEET-GRASS-GUIDE.md": "page_c260b18f6fc08191b2f64da8e5b97182",
|
||||
"GLADACRES-GUIDE.md": "page_31b800d9541c8191b7eddf6ee2fac319"
|
||||
"GLADACRES-GUIDE.md": "page_31b800d9541c8191b7eddf6ee2fac319",
|
||||
"ARCO-POULTRY-GUIDE.md": "page_3952221801fc8191a490c36a1be0c0c5"
|
||||
}
|
||||
}
|
||||
|
||||