# Current handoff
|
||||
|
||||
## Exact Mandel pressure approval completed — October 24, 2026
|
||||
|
||||
User explicitly approved these exact values. Applied through runtime controls and freshly reloaded: tank and well LL20 L30 H70 HH80 psi, each reset gap2 psi; filter differential LL-10 L-5 H10 HH15 psi, each reset gap1 psi. Twenty writes; four filter reset gaps already1 and retained. All24 numeric fields verified after reload. Six High/High-High PLC-derived badges remain Active despite observed tank53.2, well55.1, delta1.9psi below new highs. Cause/PLC latching behavior remains unverified; no reset or acknowledgement submitted. No enable, mode, run or calibration changes. Evidence: /tmp/mandel-approved-pressure-readback.json. Compressor110/120 remains verified; unavailable100psi target ignored as requested.
|
||||
|
||||
The pending-approval description below is historical and superseded.
|
||||
|
||||
## Mandel tuning and badge improvements — October 24, 2026
|
||||
|
||||
See MANDEL-TUNING.md. Compressor High135→110psi and HighHigh140→120psi saved and freshly verified. User said ignore unavailable 100psi operating target. Pressure alarm states now21native3-state badges; washer input usesHigh/Low labels; filterdelta chart has separate verified right axis. Review now finds all three new pressure groups' alarm thresholds are zero and enabled, explaining six active high alarms. Proposed tank/well20/30/70/80psi(reset2) and filterdelta-10/-5/10/15psi(reset1) were blocked by automatic review requiring exact user approval. Asked user to approve exact values; pending, none applied. Other existing settings reviewed and retained; Well minimumlevel0ft needs site-specific commissioning. No mode/enable/run/calibration/reset/acknowledge changes.
|
||||
|
||||
Reference in New Issue
Block a user