docs: record verified Well 10 chlorine write-target correction
This commit is contained in:
+1
-1
@@ -10,7 +10,7 @@ Catalogs now cover 202 pages: KAV Main Mill 43, East Mill 4, Main Water 29, East
|
||||
|
||||
Scope was production Configure Pages and native Copy inspection only. No pastes, site saves, register writes, device actions or operational tests. Development equivalence was not checked. User's two work environments are dev.atomhmi.com and atomhmi.com (observed production host www.atomhmi.com).
|
||||
|
||||
Notable unresolved findings: Well 10 New chlorine display reads g_well10ChemPPM but writes g_well1ChemPPM; Lazy B Well 3 timer fields reference wellNW1; East Water Wells has two Well 29 series, one bound to Well 30. These are documented, unchanged configurations, not verified corrections.
|
||||
Follow-up correction, October 21, 2026: the user authorized fixing production KAV Main Water Well 10 New. Its chlorine field's updateRegister changed from water:g_well1ChemPPM to water:g_well10ChemPPM, matching its display expression. The page saved successfully; a fresh reload/reopen confirmed persistence and only this field changed among 37 captured form controls. No chlorine setpoint value was submitted or dosing behavior tested. See KAV-GUIDE.md. The preceding read-only scope describes the baseline survey, before this separately authorized configuration edit. Remaining unchanged findings: Lazy B Well 3 timers reference wellNW1; East Water Wells has two Well 29 series, one bound to Well 30.
|
||||
|
||||
## Original October 20 coverage
|
||||
|
||||
|
||||
Reference in New Issue
Block a user