Mandel settings expansion

Later simulation testing, lighting controls, washer digital-limit feedback, and Copy/Paste discoveries are recorded in ATOMHMI-PLAYBOOK.md. The verification below describes the earlier build before those tests.

Updated October 20, 2026. The pressure-washer sensor is not active yet, as confirmed by the owner. Its pressure reading is not a commissioning reference.

Delivered adjustments

Page Editable settings
Chicken Coop Heating setpoint, cooling setpoint, daily fan target (hours); four temperature alarm thresholds and low/high reset hysteresis
Air Compressor Auto/Manual selector; four pressure alarm thresholds and low/high reset hysteresis
Pressure Washer Auto/Manual selector; four pressure alarm thresholds and low/high reset hysteresis; inactive-sensor commissioning note
Ventilation House fan speed (0–100%); four negative-pressure alarm thresholds and low/high reset hysteresis
Water Usage Four house-flow alarm thresholds and low/high reset hysteresis

Tap a bordered numeric value, enter a new value, and press Save to apply it. Cancel leaves the controller value unchanged. Auto/Manual switches apply their selected mode. Existing Start/Stop buttons remain available on the compressor and washer pages.

All existing threshold values, operating modes, and alarm-enable logic were preserved during this build. Exposing editable settings did not apply new setpoints or switch modes.

Register mapping

For each prefix below, Low, Low-Low, High, and High-High threshold fields read and write the corresponding <prefix>_limits_<level>_in_sp register, where level is lo, lolo, hi, or hihi. Low/High Reset Hysteresis fields use <prefix>_limits_lo_in_hyst and <prefix>_limits_hi_in_hyst.

Page Prefix Display units
Air Compressor g_airPressure psi
Pressure Washer g_pressureWasherPres psi; sensor inactive
Chicken Coop g_coopTemp °C
Ventilation g_negAirPres PLC engineering units (EU)
Water Usage g_houseFlow PLC engineering units (EU)

The Manage Alarms catalog contains corresponding High, High-High, Low, and Low-Low alarm records for all five groups. These are alarm adjustments, not invented operating-pressure controls. Alarm activation still follows the controller's existing enable configuration.

Additional controls:

  • Heating setpoint: main:g_coopHeatSP, direct numeric read/write.
  • Cooling setpoint: main:g_coopCoolSP, direct numeric read/write.
  • Daily fan target: main:g_coopDailyFanDur, displayed as register / 3,600,000 and written as user value × 3,600,000. Entry range 0–24 hours.
  • House fan speed: main:g_houseFanSpeed, direct numeric read/write with entry range 0–100%.
  • Compressor mode: main:g_airCompressor_in_autoMode, Auto = 1, Manual = 0.
  • Washer mode: main:g_pressureWasher_in_autoMode, Auto = 1, Manual = 0.

Enabled polling for the 30 threshold/hysteresis registers and the two mode registers. Existing coop setpoint and fan-speed registers were already enabled. This changes register availability, not the PLC's alarm-enable settings.

Verification

  • Observed page-save confirmations and reopened all five saved runtime pages.
  • Heating entry opened with its existing value of 10 °C, then was cancelled.
  • High-High temperature alarm entry opened at its existing 35 °C, then was cancelled.
  • Daily fan entry opened at 1 hour and showed 0–24 hour limits, then was cancelled.
  • Fan-speed entry opened at 0% and showed 0–100% limits, then was cancelled.
  • Checked the saved threshold readouts and Auto/Manual selectors without toggling modes.
  • No PLC register values were written, no alarm thresholds were changed, and no equipment commands were run.

The write targets and conversion expressions were configured and reviewed; a submitted write was not tested. Alarm numeric fields preserve signed engineering values and do not enforce cross-field ordering. They should be set coherently for the installation. No arbitrary alarm bounds, delay-unit conversions, or sensor calibration changes were introduced.

Screenshots and the alarm/register audit are under artifacts/mandel/ with settings in their filenames. The Chicken Coop page is left open for review.