| 1 |
#Version: 2.0.0.1 |
| 2 |
ID;ObservationType;Details1;Details2;Details3;Details4;Details5;Details6;Deactivation;Class;Message;Message2;OnDelayTime;OffDelayTime;Latch1;Latch2;HigherPrioAlarm |
| 3 |
0;Digital;g.destEn[0];=;TRUE;;;;;Info;No destination bin assigned for receiving;;;;;; |
| 4 |
1;Digital;g.rollerDestEn[0];=;TRUE;;;;;Info;No destination bin assigned for mill;;;;;; |
| 5 |
2;Digital;g.bin01HLS.alm.out_default AND g.destEn[1];=;TRUE;;;;;Info;Bin 1 high level has been tripped;;;;;; |
| 6 |
3;Digital;g.bin02HLS.alm.out_default AND g.destEn[2];=;TRUE;;;;;Info;Bin 2 high level has been tripped;;;;;; |
| 7 |
4;Digital;g.bin04HLS.alm.out_default AND g.destEn[3];=;TRUE;;;;;Info;Bin 4 high level has been tripped;;;;;; |
| 8 |
5;Digital;g.bin05HLS.alm.out_default AND g.destEn[4];=;TRUE;;;;;Info;Bin 5 high level has been tripped;;;;;; |
| 9 |
6;Digital;g.bin06HLS.alm.out_default AND g.destEn[5];=;TRUE;;;;;Info;Bin 6 high level has been tripped;;;;;; |
| 10 |
7;Digital;g.bin07HLS.alm.out_default AND g.destEn[6];=;TRUE;;;;;Info;Bin 7 high level has been tripped;;;;;; |
| 11 |
8;Digital;g.bin08HLS.alm.out_default AND g.destEn[7];=;TRUE;;;;;Info;Bin 8 high level has been tripped;;;;;; |
| 12 |
9;Digital;g.bin09HLS.alm.out_default AND g.destEn[8];=;TRUE;;;;;Info;Bin 9 high level has been tripped;;;;;; |
| 13 |
10;Digital;g.bin10HLS.alm.out_default AND g.rollerDestEn[2];=;TRUE;;;;;Info;Bin 10 high level has been tripped;;;;;; |
| 14 |
11;Digital;(g.bin11HLS.alm.out_default AND g.rollerDestEn[3]);=;TRUE;;;;;Info;Bin 11 high level has been tripped;;;;;; |
| 15 |
12;Digital;g.binEn[0];=;TRUE;;;;;Info;No source bin assigned for receiving;;;;;; |
| 16 |
13;Digital;g.rollerBinHLS.alm.out_unlatched AND g.destEn[9] AND NOT g.p01.in_autoMode;=;TRUE;;;;;Info;Roller overhead bin full;;;;;; |
| 17 |
14;Digital;g.rollerBinLLS.alm.out_unlatched;=;FALSE;;;;;Info;Roller overhead bin empty;;;;;; |
| 18 |
15;Digital;IO.IOBase_1.out_commFault.out_default;=;TRUE;;;;;Warning;IO Base 1 Comm Fault;;;;;; |
| 19 |
16;Digital;NOT g.rollerBinLLS.debounce.out_val AND g.m02.out_run;=;TRUE;;;;;Info;Mill overhead empty timeout. Mill shut down triggered;;;;;; |
| 20 |
17;Digital;g.hlShutdown AND NOT g.rollerFillAuto;=;TRUE;;;;;Info;Receiving Destination bin full. Receiving shut down triggered;;;;;; |
| 21 |
18;Digital;g.ovldAlm[0].out_default;=;TRUE;;;;;Warning;Receiving Leg overload tripped;;;;;; |
| 22 |
19;Digital;g.ovldAlm[1].out_default;=;TRUE;;;;;Warning;Receiving Drag overload tripped;;;;;; |
| 23 |
20;Digital;g.ovldAlm[2].out_default;=;TRUE;;;;;Warning;Bin 6 Auger overload tripped;;;;;; |
| 24 |
21;Digital;g.ovldAlm[3].out_default;=;TRUE;;;;;Warning;Bin 8 Auger overload tripped;;;;;; |
| 25 |
22;Digital;g.ovldAlm[4].out_default;=;TRUE;;;;;Warning;Bin 9 Auger overload tripped;;;;;; |
| 26 |
23;Digital;g.ovldAlm[5].out_default;=;TRUE;;;;;Warning;Bin 1 Auger overload tripped;;;;;; |
| 27 |
24;Digital;g.ovldAlm[6].out_default;=;TRUE;;;;;Warning;Bin 7 Auger overload tripped;;;;;; |
| 28 |
25;Digital;g.ovldAlm[7].out_default;=;TRUE;;;;;Warning;Bin 7 Drag overload tripped;;;;;; |
| 29 |
26;Digital;g.ovldAlm[8].out_default;=;TRUE;;;;;Warning;Bin 5 Auger overload tripped;;;;;; |
| 30 |
27;Digital;g.ovldAlm[9].out_default;=;TRUE;;;;;Warning;Bin 2 Auger overload tripped;;;;;; |
| 31 |
28;Digital;g.ovldAlm[10].out_default;=;TRUE;;;;;Warning;Roller Mill overload tripped;;;;;; |
| 32 |
29;Digital;g.ovldAlm[11].out_default;=;TRUE;;;;;Warning;Medicator overload tripped;;;;;; |
| 33 |
30;Digital;g.ovldAlm[12].out_default;=;TRUE;;;;;Warning;Discharge Leg overload tripped;;;;;; |
| 34 |
31;Digital;g.ovldAlm[13].out_default;=;TRUE;;;;;Warning;Discharge Utrough overload tripped;;;;;; |
| 35 |
32;Digital;g.receivingSpeed.limits.lo.alm.out_default;=;TRUE;;;;;Warning;Receiving Leg low speed alarm;;;;;; |
| 36 |
33;Digital;g.dischargeSpeed.limits.lo.alm.out_default;=;TRUE;;;;;Warning;Discharge Leg low speed alarm;;;;;; |
| 37 |
34;Digital;g.receivingSpeed.limits.lolo.alm.out_default;=;TRUE;;;;;Warning;Receiving Leg low low speed alarm system shut down;;;;;; |
| 38 |
36;Digital;IO.IOBase_2.out_commFault.out_default;=;TRUE;;;;;Warning;IO Base 2 Comm Fault;;;;;; |
| 39 |
35;Digital;g.dischargeSpeed.limits.lolo.alm.out_default;=;TRUE;;;;;Warning;Discharge Leg low low speed alarm system shut down;;;;;; |
| 40 |
37;Digital;g.recLegCur.limits.hi.alm.out_default;=;TRUE;;;;;Warning;Receiving Leg Hi Current;;;;;; |