Sweet Grass site guide

Verified through production Configure Pages and native element Copy on 2026-10-21 (America/Edmonton). This was a read-only context survey: no page saves, pastes, register writes, alarm changes, device actions, or operational command tests. Bindings describe the configured UI, not proven PLC behavior. No credentials or camera/map endpoints are retained.

Identity and coverage

Production: https://www.atomhmi.com/site_sweetgrass/
Configure: https://www.atomhmi.com/site_sweetgrass/configure_pages

Catalog remains 51 pages. PAGE-INVENTORY.md preserves the full list from October 20. October 21 refreshed the catalog and selected active pages, resolving both previous motor-tree inspection gaps. Combined historical coverage now includes every listed page tree, but this is not an audit of every element's behavior.

Useful starting pages

Page Slug Roots / element count observed October 21
Overview overview Main Selection; 49
Center Receiving center_receiving Control Row; 228
South Receiving south_receiving Control Row; 83
Receiving Sequence receiving_sequence Control Row; 100
Crimping crimping Control Row; 103
Groater groater Control Row; 313
Shipping shipping Control Row; 103
dryer dryer Dryer Chart Div + Overview Row; 137
Power Main power_main Menu + Main Row + Table; 186
Power Dryer power_dryer Menu + Main Row + Table; 186
Motors motors Motors; 1,435
old Motors old_motors Motors; 1,246
Receiving PID Tuning receiving_pid_tuning no roots/elements

Use Overview for compact status cards; Center/South Receiving for routing and sequence controls; Groater for dropdown and equipment control; Shipping for four-state indicators and destination selection; dryer for chart-plus-controls; Power pages for chart/readouts/tables. Empty Receiving PID Tuning is not an established tuning interface.

Motor tree gap resolved

Motors and old Motors both loaded on October 21. Native Copy exported each whole root; active Motors has 103 direct children and old Motors has 83. These include menu/group structure, so do not interpret the counts as a proven motor count.

Active groups include dryer-style m02_01 through m90 families and other groups named M001, M002, M016, M101, M202, M301, etc. Group names and prefixes differ; inspect each intended unit rather than applying one global rename.

Representative active dryer motor m02_01:

Function Configured binding
Auto/Manual main:dryer_g_m02_01_in_autoMode; 1/0
Start main:dryer_g_m02_01_in_manFwd; writes 1
Stop main:dryer_g_m02_01_in_manStop; writes 1
Hertz display main:dryer_g_m02_01_out_speedActHz
Hertz write target main:dryer_g_m02_01_in_manSpeedRef; direct value
Time since start main:dryer_g_m02_01_out_tss multiplied by 1000; non-editable HH:mm:ss

The editable Hertz field intentionally separates actual-speed display from manual demand target. A configured target on the non-editable time display does not authorize writing an output.

For large trees, use the root's direct Copy control rather than resolving every descendant button. Reload a clean Configure Pages session before each large page; accumulated previews caused timeouts during this survey. See ATOMHMI-PLAYBOOK.md.

Prior verified context retained

The October 20 study in SITE-STUDY.md established:

  • Device IDs global (Global) and main (Main PC).
  • Main PC slave labels Codesys PLC, Groater PLC, Main PLC, SG Dryer, Shipping PLC, Terminal.
  • Page → device-qualified register → slave → PLC tag mapping. Register presence does not establish enabled/updating/logged state.
  • Overview's six-state indicator references main:dryer_g_m77_01_out_status.
  • Center Receiving Start targets main:recvSeqStart with value 1.
  • A Center Receiving ratio reads main:dryer_g_centRecBin21Ratio but writes main:dryer_g_centRecBin21RatioSel, writeValue=value. Limits checkbox was false despite populated 0/100.
  • Sample dryer status address: tag sg_dryer.g.m77_01.out_status; enabled On Change/one-second polling, logging disabled in that earlier inspected definition.

These are dated prior observations, not a new register-table audit on October 21. The prior counts of 20,055 register definitions and 1,538 alarm definitions are historical, not freshly verified totals.

Future work boundaries

Use this guide and the earlier full catalog instead of repeating the general survey. Verify current Title/slug and the particular subtree before editing. Preserve roots, location anchors, read/write distinctions, state mappings, chart series/scales/navigator and time conversions.

No PLC commands, setpoint writes, motor tests, alarm-latching changes or device actions were performed. History retention, alarm notification/latching and physical interlocks remain outside this survey. Old/test page names do not establish which content is current or safe to modify.

Bin G Hi-Hi enable/disable investigation — October 21, 2026

User requested an Atom HMI enable/disable control for Sweet Grass Bin G Hi-Hi. Inspected production https://www.atomhmi.com/site_sweetgrass/ after reading repository instructions and cloud knowledge/site guide. No site changes or operational writes were made; target alarm path needs clarification.

Verified in Main PC (main):

  • HMI alarm ALM-436 has description ALM-436, message "Bin G Full", calculation |{register:main:Alm436}|, enabled true, latching false, Warning importance, one-second update, zero on/off delays, notification groups Atom Notifications and Default Notifications.
  • Source register Alm436 is enabled, observed 0, Main PLC slave, Modbus slave 1, Coil 4427, Bit format, bit 0, Swapped checked; On Change/two-second update, logging disabled.
  • Separate Codesys register clean_g_binG_lvl_limits_hihi_alm_in_en has description Bin G level and address { "tag": "sg_cleaning.g.binG_lvl.limits.hihi.alm.in_en" }. Enabled is unchecked; configured On Change/one-second update and logging disabled. No current value was available. This is a candidate alarm-enable input, not a verified control for ALM-436.
  • Separate clean_g_binG_lvl_limits_hihi_in_en, ...hihi_in_sp, ...hihi_out and ...hihi_alm_out definitions also exist with Enabled No. Do not conflate threshold enable with alarm enable or infer PLC write ownership from names.
  • clean_g_binG_lvl_out_eu is enabled and observed about 84.45–84.56; this readback does not establish the alarm path.
  • Main PC tables currently report 20,055 registers and 1,538 alarms. Searching Bin alarm messages found ALM-436 but no Bin G Hi-Hi message.
  • Navigation Bins opens page_bin_2 (editor Title Bin 2, slug bin_2), which displays Bin G among the bin gauges. The separately configured Bins page (slug bins) displays H/J/bagging/K/L/M/N and is not the navigation target.

Asked whether the intended control is the Codesys level Hi-Hi alarm or the existing Main PLC Bin G Full alarm. Next: resolve the intended path and verified writable setting, add a supported native enable/disable control on the relevant operator page, preserve existing state, save/reload and verify configuration. Do not write Alm436 or an alarm output to simulate enable. No polling, thresholds, alarm definitions, notifications, latching, pages, or equipment commands changed during this investigation.

Alarm history lookup — October 21, 2026

User requested checking whether any Bin G alarm previously occurred. Opened the alarm icon → Alarm History at https://www.atomhmi.com/site_sweetgrass/alarm_history. Requested Last 30 Days (September 22–October 21, 2026), then freshly reloaded and requested October 21, and finally Yesterday (October 20). Every attempt remained on Loading... without a history table, records, or an explicit empty-result message. No browser warning/error logs were captured. Occurrence, timestamps and retention therefore remain unverified; this is not evidence of no prior Bin G alarms. No acknowledgement, reset, alarm edits, register writes or page saves performed. User-confirmed update on October 21, 2026: Atom HMI was just updated and alarm logs moved to a new database; previous history is no longer available. This supersedes the earlier plan to retry for pre-migration records. Historical Bin G occurrences cannot be determined from the current database. The migration explains unavailable prior history, but the cause of the observed Loading... UI was not independently established. The intended Bin G enable/disable alarm path remains unresolved; determine it from current configuration or user/PLC confirmation.

Bin Hi/Hi-Hi alarm source audit — October 21, 2026

User-confirmed direction: the old Main Plant PLC is a Horner; alarms formerly on it should move to the new Codesys plant PLC. This audit reads HMI configuration, not PLC source logic. Configured source slave establishes where Atom reads an alarm bit; it does not prove whether that PLC computes or forwards it.

Production https://www.atomhmi.com/site_sweetgrass/; device Main PC (main). Inspected 39 unique high/high-high/high-shutdown/full HMI alarm definitions and their source registers: 17 Main PLC, 5 Groater PLC, 13 Codesys PLC, 4 SG Dryer. Included equipment level messages that omit "bin"; not a full plant alarm migration audit. No site configuration saves, polling changes, acknowledgements, resets, commands or PLC writes.

Legacy Main PLC (main_plc; user identifies old Horner)

Each ALM-NNN calculation is exactly |{register:main:AlmNNN}|. All 17 source registers have polling Enabled checked. Modbus slave ID 1, Coil addresses shown as configured (no address-base conversion).

Equipment / messages HMI alarm IDs Source register IDs Coils HMI alarm enabled
Air Screen Bin Level High Alarm / High Shutdown ALM-014 / ALM-015 Alm014 / Alm015 4005 / 4006 Both Yes
Indent Bin Level High Alarm / High Shutdown ALM-019 / ALM-020 Alm019 / Alm020 4010 / 4011 Both Yes
Grader Bin Level High Alarm / High Shutdown ALM-024 / ALM-025 Alm024 / Alm025 4015 / 4016 Both No
Paddy Bin Level High Alarm / High Shutdown ALM-064 / ALM-065 Alm064 / Alm065 4055 / 4056 Both Yes
Bin H Level Hi / HiHi ALM-124 / ALM-125 Alm124 / Alm125 4115 / 4116 Both Yes
Bin J Level Hi / HiHi ALM-134 / ALM-135 Alm134 / Alm135 4125 / 4126 Both Yes
Bagging Bin Level Hi / HiHi ALM-139 / ALM-140 Alm139 / Alm140 4130 / 4131 Hi No; HiHi Yes
Bin 21 High Level ALM-343 Alm343 4334 Yes
Screenings Bin Full ALM-435 Alm435 4426 Yes
Bin G Full ALM-436 Alm436 4427 Yes

Other PLCs must remain distinct

Groater PLC (groater_plc), Modbus slave 1, Coil: ALM-1410 Bin H Hi → Alm1410/4401; ALM-1411 Bin H HiHi → Alm1411/4402; ALM-1412 Bin J Hi → Alm1412/4403; ALM-1413 Bin J HiHi → Alm1413/4404; ALM-1414 Bin i Hi → Alm1414/4405. All HMI alarms and source polling enabled. Calculations reference their respective main:AlmNNNN register. The H/J entries are not the same source as the Main PLC "Level" entries.

Codesys PLC (codesys_plc): existing HMI alarm IDs and source register IDs are identical:

  • clean_g_bin01_lvl_limits_hi_alm_out through bin06, plus bin11: messages Bin 1–6 / 11 High Level; all HMI alarms and polling enabled. Addresses individually verified: sg_cleaning.g.binNN_lvl.limits.hi.alm.out.
  • clean_g_m08_lvl_limits_hi_alm_out and ...hihi_alm_out: M08 Air Screen Level Hi / Hi Hi.
  • clean_g_m12_lvl_limits_hi_alm_out and ...hihi_alm_out: M12 Grader Level Hi / Hi Hi.
  • clean_g_m14_lvl_limits_hi_alm_out and ...hihi_alm_out: M14 Paddy Level Hi / Hi Hi. All six equipment alarms and source polling enabled; addresses individually verified as sg_cleaning.g.mNN_lvl.limits.hi.alm.out or .hihi.alm.out. Every calculation directly references its matching main: register. Thus Air Screen/Paddy retain enabled Horner and enabled Codesys alarm paths; Grader's Horner definitions are already disabled. Similar equipment names establish migration candidates, not proven equivalence of thresholds, delays, inputs or shutdown logic.

SG Dryer (sg_dryer): four enabled HMI alarms and enabled source registers: dryer_g_bin21Lvl_limits_hi_alm_out, ...bin21Lvl_limits_hihi_alm_out, ...bin22Lvl_limits_hi_alm_out, ...bin22Lvl_limits_hihi_alm_out. Direct matching-register calculations. Addresses individually verified as sg_dryer.g.bin21Lvl/22Lvl.limits.hi/hihi.alm.out. Do not classify these as the Codesys plant slave merely because addresses use symbolic tags.

Replacement gaps and next steps

  • Indent: candidate Codesys registers clean_g_m10_lvl_limits_hi_alm_out and ...hihi_alm_out both exist, individually mapped to codesys_plc tags sg_cleaning.g.m10_lvl.limits.hi/hihi.alm.out, but polling disabled. Alarm search m10_lvl returned over/under fault definitions only, no Hi/HiHi definitions.
  • Bin G: clean_g_binG_lvl_limits_hihi_alm_out individually verified on codesys_plc at sg_cleaning.g.binG_lvl.limits.hihi.alm.out; polling disabled. Register table also shows Hi output disabled. Alarm search binG returned no matches; "Bin G Full" ALM-436 still reads Main PLC. Earlier alarm-enable candidate .hihi.alm.in_en remains unpolled and untested.
  • Numbered bins 1–6 and 11 have HiHi output register definitions, polling disabled; inspected bin-message inventory has only their Hi alarm definitions.
  • Register tables also show A/B/C/F/G/T Hi and HiHi output definitions unpolled. Their complete mappings and intended service were not audited.
  • No Codesys replacements for Main PLC Bin H/J/Bagging/Screenings were verified in this pass. Bin 21 has a verified SG Dryer alternative, not an established plant-Codesys replacement.
  • Next: compare controller program mapping, sensor identity, thresholds, delays, enable ownership and shutdown semantics before replacing sources. Start with existing Air Screen/Grader/Paddy Codesys pairs, then address Indent and Bin G gaps. Preserve alarm messages, notifications and required behavior, and avoid duplicate notifications during cutover. Do not retire Groater/Dryer alarms as part of a Horner-only migration without verifying scope.
  • The user-confirmed database migration means pre-update alarm history is unavailable; it cannot establish whether a legacy path was used.